Differential Pressure Transmitter – testo 6321

Description

With the testo 6321 you get a differential pressure transmitter with a good price-performance ratio for applications in air conditioning and ventilation technology. Automated building services need more and more accurate monitoring, which also means increasing requirements for measuring and control technology. The testo 6321 transmitter for differential pressure meets these requirements through high-precision measurement of differential pressure with long-term stability. It helps you to ensure optimum system function, to optimize climate conditions and to save energy.

testo 6321 differential pressure transmitter – the applications
Industrial and commercial buildings, e. g. in production and storage
Office and administration buildings
Sales areas and exhibition halls
Museums and libraries
School buildings, hotels, clinics, etc.

USPs

• Pressure transmitter for measuring differential pressure in the 100 Pa to 2 bar measuring range
• Magnetic valve for automatic zero-point adjustment guarantees high temperature independent accuracy and long-term stability
• Alignment and analysis save time and costs for commissioning and maintenance
• Available with and without display

Delivery Scope

testo 6321 differential pressure transmitter with selectable measuring range between 100 Pa and 2,000 hPa, selectable signal outputs and optional display (depending on the configuration).

Downloads

Download Datasheet Instruction manual

Application Image

Compressed Air Flow Meter – testo 6441

Description

In industrial companies, compressed air is an important source of energy, but one which can also incur high costs. Precise measuring and control technology creates transparency when it comes to compressed air consumption and can help you save energy, reduce costs and implement a targeted environmental management system (e.g. as per ISO 50.001 or ISO 14.001).

The testo 6441 compressed air flow meter enables you to carry out accurate compressed air consumption measurements, consumption and leak monitoring and flow measurements in your compressed air system. The compressed air flow meter can also be used to carry out a peak load analysis in order to determine whether you are generating compressed air of sufficient capacity. Overall, these measures can help you find potential for savings or prevent unnecessary investment costs.

Overview of the technical advantages offered by the testo 6441 compressed air flow meter

The testo 6441 compressed air flow meter is also a transmitter, which converts the measured parameter into a standardized electrical signal. The transmitter can therefore be integrated into systems (e.g. compressed air systems), making it a key instrument in measuring and control technology. The testo 6441 compressed air flow meter also offers the following advantages:

– Ultimate flexibility with a variety of signal outputs: analog output, pulse output, 2 switching outputs. You will therefore be equipped for any kind of application, whether that is consumption measurement, consumption or leak monitoring or even flow measurement
– Integrated totalling function: the practical totaliser means that no additional analysis units are needed to calculate the total consumption
– Ultimate accuracy: the precisely defined inner diameter (DN15) enables adjustment to standard volumetric flow, providing a high degree of measuring accuracy. This is an advantage compared with standard penetration probes, which calculate volume flow on the basis of measured flow and indicated pipe diameter – a procedure that is more vulnerable to error than measurement using the compressed air flow meter
– Easy operation with a high degree of flexibility: parametrization of signal outputs, switching of physical units, signal delay, signal attenuation are all possible
– Measurement according to the calorimetric principle: no pressure loss during measurement
– Other advantages: no temperature compensation required, quick response time, robust sensor, optimized accuracy thanks to integrated inflow and outflow sections.

USPs

• Measurement of norm volume flow in the measuring range 0.25 to 700 m3/h (DN15 to DN50 or ½’’-2’’);
• Consumption quantity in m3; media temperature in °C
• Highest flexibility thanks to different signal outputs:
– Analog output 4 to 20 mA (4-wire)
– Pulse output
– 2 switch outputs (parameterizable: consumption or volume
– flow-dependent, opener, closer, hysteresis, window)
• Built-in totalizer, even without additional analysis unit
• Operating menu with LED display.

Delivery Scope

testo 6441 compressed air flow meter with integrated inflow/outflow section, diameter DN15 (½”), with analog, pulse and switching output.

Downloads

Download Datasheet Instruction manual

Application Image

Dewpoint Transmitter – testo 6743

Description

Air, compressed air and gases are used in all areas of industry. Humidity and moisture are generally undesirable because they can cause damage or impair the quality of the end product. The use of measuring and control technology is recommended in order to monitor humidity in the network and prevent damage.

Our testo 6743 dew point transmitter was designed specifically for measuring trace humidity in compressed air or dry air. It boasts a polymer humidity sensor which features a high degree of accuracy and long-term stability.
Technical advantages offered by the testo 6743 dew point transmitter
High accuracy: the testo 6743 dew point transmitter uses the Testo polymer sensor to measure humidity with a high degree of precision – up to ±1 K at 0 °Ctd (+32 °Ftd)
Scalable analog output: the dew point transmitter converts the measured values into a standardized electrical signal, whereby the analog output can be scaled as required (4 to 20 mA)
Alarm plug with 2 integrated switching outputs (optional): use the switching contact plug for MAX monitoring
Practical format: the testo 6743 dew point transmitter features a compact and user-friendly design. For example, the housing can be rotated by 350°, enabling optimum alignment of the display
Display with operating menu: convenient operation and on-site read-out of readings

Use the dew point transmitter to prevent damage (e.g. in refrigeration dryers or membrane dryers). This can save you a considerable amount of money, because if the quality of the end product is impaired in any way, it can prove costly. The cost of running adsorption dryers can also be reduced: accurate humidity-controlled chamber activation precisely adjusts the use of regenerated air to meet requirements – not at a preset time increment, which often creates unnecessary, excess consumption of regenerated air.

USPs

• Dew point transmitter with a measuring range of -45 °Ctd to + 30 °Ctd, G½ thread and display
• Testo polymer humidity sensor with a high degree of accuracy and long-term stability
• Freely scalable analog output (4 to 20 mA) and optional alarm plug with 2 integrated switching outputs

Delivery Scope

testo 6743 dew point transmitter to -45 °Ctd with polymer humidity sensor, display, process connection G½ thread, analog output 4 to 20 mA and optional alarm plug with 2 switching outputs.

Downloads

Download Datasheet Instruction manual

Application Image

Transmitter for Greenhouses and Laboratories – testo 6631

Description

The testo 6631 transmitter was developed specially for monitoring critical ambient conditions in greenhouses, e.g. for bio research purposes. Precise and reliable humidity measurement is indispensible in these applications, in order to avoid costs caused by failed experiments.
Process security and system availability, among the most important factors in experimental plants, are supported by a number of properties of the testo 6631 bio research transmitter.

USPs

• Transmitter with precise Testo humidity sensor that has long-term stability (±2.5 % RH)
• 2 analog outputs (humidity/temperature)
• Integrated ventilator enables flow impact onto the sensor for recording an averaged climate in the greenhouse cell
• Protection of electronics and sensor from humidity influences (such as sprinkler irrigation)

Delivery Scope

testo 6631 humidity/temperature transmitter for greenhouses and laboratories (measuring traffic lights) with selectable signal outputs and optional display (depending on the configuration).

Downloads

Download Datasheet Instruction manual

Application Image

The Air Conditioning Humidity Transmitter – testo 6621

Description

Adjustment on-site: Fast and precise via the external interface!
Of interest not only to in-house technicians or Facility Managers, but increasingly also to the responsible plant constructors: Which follow-on costs arise as a result of this transmitter?
Good news from Testo: The testo 650 or testo 400 reference instruments can be connected using the adapter 0554 6022 via the external interface – without opening the transmitter. A few operating steps in the testo 400 or testo 650 menu suffice to adjust the testo 6621 transmitter. Conclusion: Saved time and lower operating costs!

A broad variety of the testo 6621 transmitter is available. Depending on the application in a room or in a duct, the corresponding designs can be selected. A display and an external probe are available as options. You can choose between the housing colours grey and white. The testo 6621 is persuasive in technical terms thanks to the patented humidity sensors that guarantee the highest accuracy. The sensors and the analog outputs can be adjusted, analyzed and parameterized via the external interface using the P2A software.
The testo 6621 is a high-performance transmitter for a low price. It meets the increasing requirements in automated building services in terms of accuracy, reliability and safety and thereby saves energy costs.

– Highly accurate testo humidity sensor with long-term stability (±2.0% RH)
– Optional 2-line LCD display
– P2A software for parameterization, adjustment and analysis, saves time and costs in commissioning and maintenance
– Optimum calibration concept thanks to adjustment of the entire signal chain (1-point, 2-point and analog adjustment)
– Adjustment without dismantling the transmitter
– 2 analog outputs (humidity/temperature), option of 1 passive humidity and temperature analog output.

USPs

• Transmitter with 2 analog outputs (temperature/humidity)
• High-precision Testo humidity sensor with long-term stability
• Adjustment without disassembling the transmitter
• P2A software for parameterization, adjustment and analysis

Delivery Scope

testo 6621 temperature and humidity transmitter as a wall or duct version, with selectable signal outputs, 2-line display (optional), external interface for adjustment and commissioning.

Downloads

Download Datasheet Instruction manual

Application Image

Temperature and Humidity Transmitter for Critical Applications – testo 6681

Description

Industrial humidity measurement requires absolute professionalism in measuring and control technology. In industrial processes or in research-based business, the testo 6681 temperature and humidity transmitter is ideal wherever critical climatic values need to be maintained. The climate transmitter boasts a high-precision humidity sensor with long-term stability (optionally available), which enables it to achieve maximum precision: up to ±(1.0 + 0.007 * reading).

Precise measuring and control technology will help you to accurately optimize the climatic conditions in your rooms in order to prevent process disruptions and quality losses. Automation systems result in particularly efficient processes. The testo 6681 temperature and humidity transmitter can easily be integrated into individual automation systems because it features Ethernet, relay and analog outputs.

Areas of application for the testo 6681 temperature and humidity transmitter:
– Drying processes (e.g. drying tobacco, manufacturing ceramics, drying roofing tiles)
– Painting installations
– Food production (e.g. cheese processing, ripening fruit, drying pasta)
– Bio-research
– Breeding mushrooms
– High-humidity specialist fields
– Sterilization processes in an H2O2 environment
– Clean rooms
– Museums
– Storing hygroscopic substances
– Storing electronic components

Technical highlights of the testo 6681 climate transmitter

– High-quality digital probes available for the temperature and humidity transmitter: e.g. high-precision Testo humidity sensor with long-term stability, probe for high-humidity measurement, probe for trace humidity measurement, probe with a self-monitoring function (for measuring in sensor-damaging media)
– Smart probe technology: probe can be changed by the user, digital interface for the temperature and humidity transmitter, intelligent calibration concept
– Ethernet, relay and analog outputs allow for versatile use of the temperature and humidity transmitter: e.g. for control purposes (2 or optionally 3 analog outputs), for direct activation of units in the air conditioning system (optionally via relay) or even in climate monitoring systems (optionally via Ethernet connection)
– P2A software for parametrization, adjustment and analysis saves time and money during commissioning and maintenance
– Optimum protection: the climate transmitter features a robust metal housing and is protected against water jets according to protection class IP 65. Protective caps are also optionally available for specific applications (made of stainless steel, PTFE, wire mesh filter or metal). A patented H2O2 protective cap is also available to order
– 2-line display: the climate transmitter is optionally available with a display, enabling you to undertake commissioning, adjustment and analysis without using a PC
– Options for self-monitoring and early warning function: guarantees high system availability

In combination with the right probe, the testo 6681 temperature and humidity transmitter offers superior properties and benefits in comparison with a conventional climate transmitter because, when it comes to temperature and humidity measurement, this instrument features supreme, cutting-edge technology.

Note: Please note that the transmitter can only be operated with a probe. The probes are optionally available.

USPs

• High-precision Testo humidity sensor with long-term stability for high humidity applications (optional)
• Ethernet, relay and analog outputs enable optimum integration into individual automation systems
• High-quality digital probes and an intelligent calibration concept
• Self-monitoring and an early warning function ensure high system availability

Delivery Scope

testo 6681 temperature and humidity transmitter with selectable signal outputs, 2-line display (optional), Ethernet/Profibus module (optional), output of all relevant humidity variables, relay (optional), 3 analog outputs (optional).

Downloads

Download Datasheet Instruction manual

Application Image

Humidity Transmitter for Critical Climate Applications – testo 6651

Description

Not all measurement problems can be solved with “”simple”” transmitters. The testo 6651 meets special challenges. When combined with the probe series testo 660x, the testo 6651 becomes the first choice in demanding air conditioning technology as well as in many other applications. Optimum adjustment concept thanks to adjustment of the entire signal chain incl. analog adjustment Ethernet, relay and analog outputs allow optimum integration into individual automation systems Self-monitoring and early warning guarantee high system availability. Calculation and presentation of the humidity parameters relative humidity absolute humidity and dewpoint. P2A software for parameterization, adjustment and analysis saves time and costs in commissioning and maintenance. Display with multi-language display. High-quality plastic housing.

USPs

• High-precision Testo humidity sensors with long-term stability (±1.7 % RH) can be ordered for the transmitter
• Ethernet, relay and analog outputs enable optimum integration into individual automation systems
• High-quality digital probes (can be ordered) and an intelligent calibration concept
• Self-monitoring and an early warning function ensure high system availability

Delivery Scope

testo 6651 temperature/humidity transmitter for critical climate applications with selectable signal outputs, optional display, optional Ethernet module and optional relay (depending on the configuration).

Downloads

Download Datasheet Instruction manual

Application Image

Differential Pressure Transmitter – testo 6383

Description

The differential pressure transmitter testo 6383 was developed specially for monitoring low differential pressures in the measuring range from 10 Pa to 10 hPa. In cleanroom technology, the maintenance of positive pressure prevents the entry of contaminated air in critical zones. Thanks to an optional internal or external probe from the probe series 6610, the additional recording of humidity and temperature with one instrument is also possible.The testo 6383 is particularly outstanding thanks to the automatic zero-point adjustment which ensures high accuracy and long-term stability.
The integrated self-monitoring and early warning function also guarantees the operator high system availability. Measurement of differential pressure; optional: humidity and temperature.

Flat housing allows flush surface integration in the cleanroom wall. Ethernet, relay and analog outputs allow optimum integration into individual automation systems. Self-monitoring of the transmitter and early warning function guarantee high system availability. The P2A software for parameterization, adjustment and analysis saves time and costs in commissioning and maintenance. Configurable alarm management with adjustable response delay and alarm acknowledgement.

USPs

• Flat housing enables flush surface integration in the cleanroom wall
• Low measuring range from 10 Pa ensures very high precision at the lowest pressures
• Pressure transmitter for measuring differential pressure, as an option: humidity and temperature
• Automatic zero-point adjustment guarantees high temperature-independent accuracy and long-term stability

Delivery Scope

testo 6383 differential pressure transmitter with cleanroom-compliant panel design, optional humidity/temperature recording, selectable measuring range between 10 Pa and 10 hPa, selectable signal outputs and optional display (depending on the configuration).

Downloads

Download Datasheet Instruction manual

Application Image

Flue gas analyzer (O2 , CO up to 4,000 ppm) – testo 300

Description

Truly smart flue gas measurement on heating systems with the testo 300 flue gas analyzer. High-quality sensors, intuitive operation with smart-touch technology and smart features, such as efficient documentation and e-mailing of reports, will make your day-to-day work easier. testo 300 flue gas analyzer with smart-touch operation – Features Impressive measuring technology and quality O 2 sensor and CO sensor up to 4,000 ppm Longer sensor service life thanks to automatic sensor protection.
TÜV-tested according to first German Federal Immission Control Ordinance (BImSchV) and EN 50379, Parts 1-3 Integrated fine pressure Versatile probes and fast probe changes: take advantage of quick-change probes and the multi-functional handle for attaching a variety of probe shafts (each available to order separately). You can for instance use longer probe shafts for flue gas pipes with larger diameters or flexible probes for difficult-to-access measuring points Optionally available probes and accessories for further measuring tasks, such as gas flow pressure measurement, gas pipe testing, differential temperature measurement and ambient CO measurement.
Smart, intuitive, efficient: easy operation in day-to-day work Smart-touch display for intuitive operation of the flue gas analyzer: the display responds without delay – just as easy as on your smartphone Get the measurement result faster: clearly structured measurement menus for all relevant measurements Create documentation (including measuring value, measuring location, customer data) easily on site Save PDF measurement reports directly in the instrument and always have them available Signature function: your customer can sign measurement reports directly on the instrument E-mail measurement reports directly to the office or to customers via WLAN (hotspot) Large 5-inch HD display – enables you to see all the system’s parameters immediately Testo interface function for direct data transfer of measuring values to industry/customer-specific software* Ready to use straight away: in standby mode, the testo 300 is ready to measure at the touch of a button.
Use it straight away with the next customer – because you no longer need to wait for the end of the zeroing phase Integrated Bluetooth ® interface: immediate printout of the measuring values on site with the appropriate printer *Note: the manufacturer has to integrate an interface into the industry software to use the function Other advantages 10-hour rechargeable battery life: an average measurement period of 2 hours means the flue gas analyzer is capable of being used for one week Integrated, extra-strong magnets for easy fixing during the measuring process

USPs
  • Intuitive measurement menus and the fast-response Smart-Touch display ensure easy operation – as on your smartphone
  • Including O 2 and CO sensor up to 4,000 ppm
  • Intuitive measurement menus and the fast-response Smart-Touch display ensure easy operation – as on your smartphone
  • Creation of documentation directly on site and e-mailing of reports
Delivery Scope

testo 300 flue gas analyzer with O 2 and CO sensor up to 4,000 ppm, USB mains unit

Downloads

Download Datasheet Instruction manual

Application Image

Technical Details

Temperature – TC Type K (NiCr-Ni)
Measuring range -40 to +1200 °C
Accuracy ±0.5 °C (0.0 to +100.0 °C)
±0.5 % of mv (Remaining Range)
Resolution 0.1 °C (-40 to +999.9 °C)
1 °C (Remaining Range)

Differential Pressure – Piezoresistive
Measuring range -100 to +200 hPa
Accuracy ±0.5 hPa (0 to +50.0 hPa)
±1 % of mv (+50.1 to +100.0 hPa)
±1.5 % of mv (+100.1 to +200 hPa)
Resolution 0.01 hPa

Flue gas O₂
Measuring range 0 to 21 Vol.%
Accuracy ±0.2 Vol.%
Resolution 0.1 Vol.%

Differential Pressure flue gas Draught – Piezoresistive
Measuring range -9.99 to +40 hPa
Accuracy ±0.005 hPa (+0 to +0.1 hPa)
±0.02 hPa (+0.1 to +3.00 hPa)
±1.5 % of mv (3.01 to +40 hPa)
Resolution 0.001 hPa (0 to 0.1 hPa)
0.01 hPa (Remaining Range)

Flue gas degree of effectivity, Eta (calculated)
Measuring range 0 to 120 %
Resolution 0.1 %

Flue gas loss (calculated)
Measuring range 0 to 99.9 %
Resolution 0.1 %

Flue gas CO₂ calculation (calculated from O₂)
Measuring range Display range 0 to CO₂ max
Accuracy ±0.2 Vol.%
Resolution 0.1 Vol.%

Flue gas CO (without H₂-compensation)
Measuring range 0 to 4000 ppm
Accuracy ±20 ppm (0 to 400 ppm)
±5 % of mv (401 to 2000 ppm)
±10 % of mv (2001 to 4000 ppm)
Resolution 1 ppm

Ambient CO
Measuring range 0 to 2000 ppm
Accuracy ±10 ppm (0 to 100 ppm)
±10 % of mv (101 to 2000 ppm)
Resolution 1 ppm

General technical data
Operating humidity 15 to 90 %RH non-condensing
Dimensions 244 (including probe connection) x 98 x 59 LxWxH
Operating temperature -5 to +45 °C
Protection class IP40
Product colour black/orange
Display type 5.0″” touch display, HD 1280*720 pixels, IPS (160 k)
Power supply Rechargeable battery, USB mains unit
Guarantee Gas sensors (O₂, CO) 24 months; rechargeable battery: 12 months; Thermocouple 12 months
Authorizations TÜV-tested according to 1st German Federal Immission Control Ordinance (BImSchV) EN 50379, Parts 1-3
Warranty conditions https://www.testo.com/guarantee
Memory 1,000,000 measuring values
Storage battery type Lithium ion battery
Battery life 10 h
Storage temperature -20 to +50 °C
Weight approximately 800 g
Charging temperature 0 to +45 °C

Differential Pressure 4 Pa measurement – Piezoresistive
Measuring Range -50 to +50 Pa
Accuracy ±0.3 Pa (< 10 Pa) ±3 % of mv (Remaining Range) Resolution 0.1 Pa